3.13 Configuration-M: 22U Rack, 22 Servers, High Voltage
This configuration shows a “best practice” for Compaq 22U racks with 22 servers in a high voltage
facility. Remote console management via the optional Remote Insight Lights-Out Edition is
recommended. The network cables are routed to the network switches located off-rack.
Configuration-M Summary
Rack Contents
Units
22 servers with all fixed or all sliding rails with cable trays
2 High Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
11 Y-power cords going to 2 PDUs in the side panels
Cables External to Rack
22 (management) network cables from the optional Remote Insight Lights-Out
Edition RJ-45 connector to external switches
22 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server.
2 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 2 dedicated 200V-240V 30A branch circuits.
Thermal: up to 21,900 BTU [This number is a worst-case. The actual
BTUs/hour will depend on the OS/application software running and the
server hardware configurations].
Weight: up to 940 lb (with sliding-rails) [The network cables are not
accounted for since most implementations route the network cables to the
ceiling-hung cable rails outside of the rack].
22 Server 22
21 Server 21
20 Server 20
19 Server 19
17 Server 17
18 Server 18
16 Server 16
15 Server 15
14 Server 14
13 Server 13
12 Server 12
11 Server 11
10 Server 10
8 Server 8
9 Server 9
7 Server 7
6 Server 6
5 Server 5
4 Server 4
3 Server 3
2 Server 2
1 Server 1
BEST PRACTICE