Ultra-Dense Server Deployment in Racks

Compaq Ultra-Dense Server Deployment in Compaq Racks 21
128H-0400A-WWEN
2.3.2 High Voltage 16A PDU (P/N 295363-002 or 295363-B32)
The 12 outlets on this PDU are grouped into two sections, and each section is protected with a 10A circuit
breaker. The total load for this PDU cannot exceed 16A. Each section of the PDU has six outlets. The total
current available for each section is 10A. The loads should be balanced amongst the two sections such that
the total per section does not exceed 10A or a total of 16A for the PDU. Figure 2-2 illustrates the outlets
and the circuit breakers.
Figure 2-2. High Voltage 16A PDU
For more information see the following reference:
"Power Distribution Unit High Voltage Models for North America and International Use, (NA CPQ #
295363-002; INT'L CPQ # 295363-B31)," at
http://www.compaq.com/products/servers/options/ups-high.html
, a web page describing the PDU
features and listing the cable part numbers.
6 Receptacles (IEC 320-C13)
6 Receptacles (IEC 320-C13)
10A
10A
Input Connector Type:
NEMA L6-20P for PDU P/N 295363-002
IEC 309-16P for PDU P/N 295363-B32