Ultra-Dense Server Deployment in Racks
Compaq Ultra-Dense Server Deployment in Compaq Racks 20
128H-0400A-WWEN
Section 4.3 details the recommended procedures on how these PDUs and associated power cords are
installed in Compaq 9000- and 7000-series racks when deploying a fully populated rack.
2.3.1 High Voltage 24A PDU (P/N 295363-003)
The 12 outlets on this PDU are grouped into four sections. Each section is protected with a 10A circuit
breaker. The total load for this PDU cannot exceed 24A. Each section of the PDU has three outlets. The
total current available for each section is 10A. The loads should be balanced amongst the four sections
such that the total per section does not exceed 10A or a total of 24A for the PDU. Figure 2-1 identifies the
outlets and the circuit breakers.
Figure 2-1. High Voltage 24A PDU
10A 10A
10A 10A
6 Receptacles (IEC 320-C13)
6 Receptacles (IEC 320-C13)
L6-30P
4 10A Breakers