Deploying ProLiant DL320 & DL360 Servers into Third-Party Racks

Deploying Compaq ProLiant DL320 and DL360 Servers into Third-Party Racks 11
13NT-1000A-WWEN
12
Figure 6: Intake
1
and Exhaust
2
vents for the ProLiant DL320 server
12
Figure 7: Intake
1
and Exhaust
2
vents for the ProLiant DL360 server
When installed in a 1U ultra-dense server deployment, airflow is sufficient to cool
ProLiant DL320 and ProLiant DL360 servers if the following criteria are met:
Ambient air temperature at the front of the unit does not exceed 35°C (95°F).
Relative humidity does not exceed 90 percent while operating.
Unrestricted airspace of at least three inches exists in front of the server.
Unrestricted airspace of at least three inches exists at the rear of the server.
Note: Cabling must not restrict airflow. The Compaq Third-Party Rack Option Kit includes a
cable management tray to provide appropriate clearance for airflow. Ensure airflow exiting the
server’s exhaust vents is unrestricted if not using the cable management tray.