Deploying ProLiant DL320 & DL360 Servers into Telecommunications (Telco) Racks
Deploying ProLiant DL320 and DL360 Servers into Telecommunication (Telco) Racks 12
13NS-1000A-WWEN
12
Figure 7: Intake
1
and exhaust
2
vents for the Compaq ProLiant DL320 server
12
Figure 8: Intake
1
and exhaust
2
vents for the Compaq ProLiant DL360 server
When installed in a 1U ultra-dense server deployment, air flow is sufficient to cool Compaq
ProLiant DL320 and ProLiant DL360 servers if the following criteria are met:
• Ambient air temperature at the front of the unit does not exceed 95°F (35°C).
• Relative humidity does not exceed 90 percent while operating.
• Unrestricted airspace of at least 3 inches is provided in front of the server.
• Unrestricted airspace of at least 3 inches is provided at the rear of the server.
Note: Cabling must not restrict airflow. The Compaq Telco Rack Option Kit includes a cable
management tray to provide appropriate clearance for airflow. Ensure airflow exiting the server’s
exhaust vents is unrestricted if not using the cable management tray.