Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks

Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 81
128H-1100B-WWEN
4.3.5.12 Low Voltage 2-PDU Cabling Diagram (18 servers in a 22U Rack)
Figure 4-16. 22U rack cabling diagram for 2 PDUs
Notes
See Section 4.3.3 for power cord information and power cord routing choices.
The low voltage PDUs shown in this figure are 24A rated.
One Vertical-Mount PDU Bracket Kit is required for this installation. The power cords that came with
the ProLiant DL360 servers can be used in this configuration.
For PDU-1, there are 9 single cables supporting 9 servers in the above figure.
No power cords should be connected to all the unused outlets marked with Ø.
PDU-1 PDU-2
1 Line (100-120V) 1 Line (100-120V)
15 A
15 A
15 A
15 A
18 Power Cords
22
21
20
19
17 Server 17
18 Server 18
16 Server 16
15 Server 15
14 Server 14
13 Server 13
12 Server 12
11 Server 11
10 Server 10
8 Server 8
9 Server 9
7 Server 7
6 Server 6
5 Server 5
4 Server 4
3 Server 3
2 Server 2
1 Server 1