Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks

Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 74
128H-1100B-WWEN
4.3.5.5 Low Voltage 4-PDU Cabling Diagram for In-Rack Local Console
(42U Rack)
Figure 4-9. 42U rack cabling diagram for 4 PDU in-rack local console.
Notes
Only up to 35 ProLiant DL360 servers are supported in this configuration.
See Section 4.3.3 for power cord information and power cord routing choices.
The low voltage PDUs shown in this figure are 24A rated. At 110V input voltage for each
ProLiant DL360 server, the current consumption can be up to 2.66A. Therefore, up to 9 servers can be
supported per PDU. With 4 PDUs, up to 36 servers can be supported in this configuration. However,
if a rack is to be populated with Server Console Switches, a keyboard and a flat panel display for the
rack to be "stand-alone," then only 35 1U spaces will be left for the servers.
One Vertical-Mount PDU Bracket Kit is required for this installation. The power cords that came with
the ProLiant DL360 servers can be used in this configuration.
No power cords should be connected to all the unused outlets marked with the symbol Ø in the
above figure.
PDU-2
PDU-1
PDU-3
PDU-4
2 Lines (100-120V)
2 Lines (100-120V)
41 Power Cords
15 A
15 A
15 A
15 A
15 A
15 A
15 A
15 A
22 Server 20
21 Server 19
20 Server 18
19 Server 17
17 Server 16
18 KVM 2 / Kybd
16 Server 15
15 Server 14
14 Server 13
13 Server 12
12 Server 11
11 Server 10
10 Server 9
35 Server 30
36 Server 31
34 Server 29
33
32 FPD
30 Server 27
31 Server 28
29 Server 26
28 Server 25
27 KVM 3
42 KVM 5
40 Server 34
41 Server 35
39 Server 33
38 KVM 4
37 Server 32
26 Server 24
25 Server 23
24 Server 22
23 Server 21
8 Server 8
9 KVM 1
7 Server 7
6 Server 6
5 Server 5
4 Server 4
3 Server 3
2 Server 2
1 Server 1