Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 73
128H-1100B-WWEN
4.3.5.4 High Voltage 4-PDU Cabling Diagram (42U Rack)
Figure 4-8. 42U rack cabling diagram for 4 PDUs
Notes
• See Section 4.3.3 for power cord information and power cord routing choices.
• The high voltage PDUs shown in this figure are 16A rated.
• Two Vertical-Mount PDU Bracket Kits with High Voltage Cables are required for this installation.
Only 21 out of 22 cables will be used.
• For PDU-1, -3 and -4, there are 5 Y-cables to support 10 servers on each PDU.
• For PDU-2, there are 6 Y-cables to support 12 servers.
• For each PDU, there are 6 or 7 remaining power outlets, but the PDU rated current capacity has been
allocated for the servers. No power cords should be connected to all the unused outlets marked
with the symbol Ø in the above figure.