4.3.5.1 High Voltage 2-PDU Cabling Diagram (42U Rack)
Figure 4-5. 42U rack high voltage diagram for 2 PDUs
Notes
• See Section 4.3.3 for power cord information and power cord routing choices.
• The high voltage PDUs shown in this figure are 24A rated.
• Two Vertical-Mount PDU Bracket Kits with High Voltage Cables are required for this installation.
All 22 cables will be used.
• *There are 11 Y-cables connected to each PDU to support 21 servers in the above figure. Ten of the
Y-cables are connected to 20 servers. The 11
th
Y-cable connects only to 1 server.
• No power cords should be connected to all the unused outlets marked with the symbol Ø in the
above figure.