Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks

Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 61
128H-1100B-WWEN
Table 3-41. Configuration-N Summary
Configuration-N Summary
Rack Contents
Units
Eighteen servers with all fixed or all sliding rails with cable trays
Two low voltage 24 A PDUs vertically mounted in the side panel compartments
Internal Cables
Eighteen power cords connected to two PDUs in the side panels (These cables
are supplied with the servers.)
Cables External to Rack
Eighteen (management) network cables connecting the optional Remote Insight
Lights-Out Edition RJ4-5 connector to the external switches
Eighteen (data) network cables connecting on-board RJ-45 to the external
switches, assuming use of only one LAN connection per server
Two input power cords connecting the rack to the external power outlets
Site Utility Requirements (worst-case)
Power: 2 dedicated 100V-120V 30 A branch circuits
Thermal: up to 18,000 BTU (This number is a worst-case scenario. The actual
BTUs/hour will depend on the OS and application software running and the
server hardware configurations.)
Weight: up to 825 lb (with sliding-rails) (The network cables are not considered
since most implementations route the network cables to the ceiling-hung
cable rails outside of the rack.)
Table 3-42. Configuration-N Parts List
Configuration-N Parts List
Description Compaq P/N Qty. Notes
Sliding rails and cable management solution
option
174575-B21 18 Optional for in-rack servicing
Remote Insight Lights-Out Edition option 157866-001 18 N.A. [See Note(a)]
Low Voltage 24A PDU option 295363-001 2 N.A. [See Note(a) & (b)]
Vertical-Mount PDU Bracket Kit 191265-B21 1 This kit contains 8 PDU
brackets. Only 4 PDU brackets
are needed
Note:
This list does not include the rack, the ProLiant DL360 servers, or the network cables.
(a) Part numbers for the regions outside N.A. are listed in Appendix B on page 94.
(b) The Low Voltage PDUs are available for N.A. and Japan.