Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks

Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 56
128H-1100B-WWEN
3.12 Configuration-L: 36U Rack, 36 Servers, Low
Voltage
This configuration shows a Compaq 36U rack with 36 servers in a low voltage facility. Remote
console management via the optional Remote Insight Lights-Out Edition is recommended for this
configuration. The network cables are routed to the network switches located off-rack.
Table 3-35. Configuration-L Summary
Configuration-L Summary
Rack Contents
Units
36 servers with all fixed or all sliding rails with cable trays
4 Low Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
36 power cords going to 4 PDUs in the side panels [These cables are supplied
with the servers.]
Cables External to Rack
36 (management) network cables from the optional Remote Insight Lights-Out
Edition RJ-45 connector to ex ternal switches
36 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server.
4 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 4 dedicated 100V-120V 30A branch circuits.
Thermal: up to 35,850 BTU [This number is a worst-case. The actual
BTUs/hour will depend on the OS/application software running and the server
hardware configurations].
Weight: up to 1,430 lb (with sliding-rails) [The network cables are not
accounted for since most implementations route the network cables to the
ceiling-hung cable rails outside of the rack].