Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 54
128H-1100B-WWEN
3.11 Configuration-K: 36U Rack, 36 Servers, 24A
High Voltage PDU
This configuration shows a Compaq 36U rack where 36 servers in a high voltage facility. Remote
console management via the optional Remote Insight Lights-Out Edition is recommended. The
network cables are routed to the network switches located off-rack.
Table 3-32. Configuration-K Summary
Configuration-K Summary
Rack Contents
Units
36 servers with all fixed or all sliding rails with cable trays
3 High Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
18 Y-power cords going to 3 PDUs in the side panels
Cables External to Rack
36 (management) network cables from the optional Remote Insight Lights-Out
Edition RJ-45 connector to external switches
36 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server.
3 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 3 dedicated 200V-240V 30A branch circuits.
Thermal: up to 35,850 BTU [This number is a worst-case. The actual BTUs/hour
will depend on the OS/application software running and the server hardware
configurations].
Weight: up to 1,418 lb (with sliding-rails) [The network cables are not
accounted for since most implementations route the network cables to the
ceiling-hung cable rails outside of the rack].