Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 52
128H-1100B-WWEN
Table 3-29. Configuration-J Summary
Configuration-J Summary
Rack Contents
Units
36 servers with all fixed or all sliding rails with cable trays
2 High Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
18 Y-power cords going to 2 PDUs in the side panels
Cables External to Rack
36 (management) network cables from the optional Remote Insight Lights-Out
Edition RJ-45 connector to external switches
36 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server.
2 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 2 dedicated 200V-240V 30A branch circuits.
Thermal: up to 34,270 BTU [This number is a worst-case. The actual
BTUs/hour will depend on the OS/application software running and the server
hardware configurations].
Weight: up to 1,406 lb (with sliding-rails) [The network cables are not
accounted for since most implementations route the network cables to the
ceiling-hung cable rails outside of the rack].