Table 3-23. Configuration H summary
Configuration-H Summary
Rack Contents
Units
35 servers with all fixed or all sliding rails with cable trays
5 KVMs, 1 FPD, 1 Keyboard, 1 Keyboard tray
2 High Voltage 24A PDUs vertically mounted in the side panel compartments.
Internal Cables
22 Y-power cords going to 2 PDUs in the side panels
40 KVM cables: [See Figure 4-22 for the cabling diagram]
35 from each server to a corresponding Server Console Switch in the rack
4 from four Server Console Switches (KVM 1-4) to the top-level Server Console
Switch (KVM 5) to cascade the KVM switches.
1 from the top-level Server Console Switch to the FPD and the
keyboard/trackball (different cable)
Cables External to Rack
35 (data) network cables from on-board RJ45 to external switches, assuming use
of only one LAN connection per server.
2 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 2 dedicated 200V-240V 30A branch circuits.
Thermal: up to 33,560 BTU [This number is a worst-case. The actual BTUs/hour
will depend on the OS/application software running and the server hardware
configurations.]
Weight: up to 1,555 lb (with sliding-rails) [The network cables are not
accounted for since most implementations route these cables to the ceiling-
hung cable rails outside of the rack.]