128H-1100B-WWEN
3.6 Configuration-F: 42 Servers, Off-Rack Local
Console, High Voltage
This configuration shows a 42U rack with a maximum number of servers in a high voltage
facility with server management via local console. Therefore, there will be several KVM cables
from each server exiting the rack, which are to be routed to KVM (Server Console) switches
located off-rack. This configuration is not recommended because of long/bulky KVM cables
and the inability to manage any server from any console.
Table 3-17. Configuration F summary
Configuration-F Summary
Rack Contents
Units
42 servers with all fixed or all sliding rails with cable trays
3 High Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
22 Y-power cords going to 3 PDUs in the side panels
Cables External to Rack
42 sets of KVM cables (126 cables worst-case) from the servers to the external
Server Console Switches
42 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server
3 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 3 dedicated 200V-240V 30A branch circuits.
Thermal: up to 41,820 BTU [This number is a worst-case. The actual BTUs/hour
will depend on the OS/application software running and the server hardware
configurations.]
Weight: up to 1,678 lb (with sliding-rails) [The KVM and the network cables are
not accounted for since most implementations route these cables to the
ceiling-hung cable rails outside of the rack.]