Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 32
128H-1100B-WWEN
Table 3-2. Configuration A Summary
Configuration-A Summary
Rack Contents
Units
42 servers with all fixed or all sliding rails with cable trays
2 High Voltage 24A PDUs vertically mounted in the side panel compartments
Internal Cables
22 Y-power cords going to 2 PDUs in the side panels
Cables External to Rack
42 (management) network cables from the optional Remote Insight Lights-Out
Edition RJ45 connectors to external switches
42 (data) network cables from on-board RJ-45 to external switches, assuming
use of only one LAN connection per server
2 input power cords from the rack to external power outlets
Site Utility Requirements (worst-case)
Power: 2 dedicated 200V-240V 30A branch circuits.
Thermal: up to 34,100 BTUs/hour [This number is a worst-case. The actual
BTUs/hour will depend on the OS/application software running and the server
hardware configurations.]
Weight: up to 1,665 lb (with sliding-rails) [The network cables are not accounted
for since most implementations route the network cables to the ceiling-hung
cable rails outside of the rack.]