2.3.3 Low-Voltage 24A PDU (P/N 295363-001 or 295363-291)
The 12 outlets on this Low-Voltage PDU are grouped into two sections, and each section is
protected with a 15A circuit breaker. The total load for this PDU cannot exceed 24A. Each
section of the PDU has six outlets. The total current available for each section is 15A. Balance the
loads between the two sections such that the total per section does not exceed 15A or a total of
24A for the PDU. Figure 2-3 illustrates the outlets and the circuit breakers.
Figure 2-3. Low-Voltage 24A PDU
For an illustration of the Low-Voltage PDU front and rear panels refer to “Power Distribution
Unit Low-Voltage Models for North America and International Use” at the following Web site:
ftp://ftp.compaq.com/pub/products/servers/Cords-powerdist-low.pdf
6 Receptacles (NEMA 5-15R)
6 Receptacles (NEMA 5-15R)
L5-30P