Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 24
128H-1100B-WWEN
2.3.2 High-Voltage 16A PDU (part number 295363-002 or 295363-B32)
The 12 outlets on this PDU are grouped into two sections, and each section is protected with a
10A circuit breaker. The total load for this PDU cannot exceed 16A. Each section of the PDU has
six outlets. The total current available for each section is 10A. Balance the loads between the two
sections so that the total load per section does not exceed 10A or a total of 16A for the PDU.
Figure 2-2 illustrates the outlets and the circuit breakers.
Figure 2-2. High-Voltage 16A PDU
For a description of the PDU features and a list of the cable part numbers refer to “Power
Distribution Unit High Voltage Models for North America and International Use, (NA CPQ #
295363-002; INT'L CPQ # 295363-B31)” at the following Web site:
http://www.compaq.com/products/servers/options/ups-high.html
6 Receptacles (IEC 320-C13)
6 Receptacles (IEC 320-C13)
Input Connector Type:
• NEMA L6-20P for PDU P/N 295363-
002
• IEC 309-16P for PDU P/N
295363-B32