Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 23
128H-1100B-WWEN
In Compaq 7000- and 9000-series racks, PDUs supporting a full rack of ProLiant DL360 servers
must be installed vertically in the rack side panels to prevent interference with the server rack
rails. Compaq Vertical-Mount PDU Bracket kits enable PDUs to be mounted vertically in the side
compartments of 7000- and 9000-series racks. Compaq offers two Vertical-Mount PDU Bracket
kits:
• Compaq Vertical-Mount PDU Bracket kit (part number 191265-B21): This kit includes eight
brackets that support four PDUs. This kit works best with low-voltage applications that use
the power cord included with the server.
• Compaq Vertical-Mount PDU Bracket with High Voltage Cables kit (part number 166097-
B21): This kit includes eleven Y-cables and four brackets that support two PDUs. This kit
works best with high-voltage, high-current PDUs. Using the Y-cables allows each power
outlet on the PDU to supply power for two servers.
2.3.1 High Voltage 24A PDU (part number 295363-003)
The 12 outlets on this PDU are grouped into 4 sections. Each section is protected with a 10A
circuit breaker. The total load for this PDU cannot exceed 24A. Each section of the PDU has
three outlets. The total current available for each section is 10A. The loads should be balanced
amongst the four sections so that the total load per section does not exceed 10A or a total of 24A
for the PDU. Figure 2-1 illustrates a high-voltage 24A PDU.
Figure 2-1. High-Voltage 24A PDU
6 Receptacles (IEC 320-C13)
6 Receptacles (IEC 320-C13)
L6-30P
4 10A Breakers