Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL360 Ultra-Dense Server Deployment in Compaq Racks 16
128H-1100B-WWEN
2.1 ProLiant DL360 Server Parameters
This section describes the abbreviated measured and specification values for ProLiant DL360
parameters. Most parameters listed in Table 2-1 will be used as a reference in discussing power
budgets and in calculating total rack configuration weight. The SA4200 option and the Remote
Insight Lights-Out Edition option are PCI cards from Compaq. Make sure that all the third-party
PCI cards used in the ProLiant DL360 server are compliant with the industry-standard PCI
specifications for dimension, weight, power and thermal requirements.
Table 2-1. ProLiant DL360 parameters
Dimensions HxWxD 1.65 x 16.75 x 25 in (4.19 x 42.55 x 63.5 cm)
Weight 24 lb as shipped (1xprocessor, 1x128 MB DIMM, 2xHDD blanks)
29.3 lb fully-configured (2xprocessors, 4xDIMMs, 2xHDDs, 1xSA4200, 1x Remote Insight
Lights-Out Edition)
• Processor: 0.2 lb (with the heat sink and clip)
• DIMM: 0.1 lb
• HDD: 1.9 lb (with the carrier)
• Remote Insight Lights-Out Edition: 0.5 lb
• SA4200: 1.0 lb
Power Rating Max. Output DC power is rated at 190W
Power Supply Efficiency (including Power Factor Correction) is rated at 65%
Max. input AC power is rated at 292W [Input Power = Output Power / Efficiency]
Max. input current rating depends on the line voltage. For example,
2.66A @110V AC (low voltage)
1.41A @208V AC (high voltage)
Thermal Dissipation Up to 1000 BTUs/hour
Temperature Rise Up to 25°C T-rise between front and rear
Relative Humidity
(non-condensing)
Operating: 8% to 90%
Non-operating: 5% to 95%
2.2 ProLiant DL360 Power and Thermal Budgeting
Note: In this document, de-rating the input power budget means not using the maximum rated
input power values for the power supply. Compaq strongly recommends the installation
planner to ensure that the de-rated power budget will satisfy all the installation
requirements, including future upgrade plans.
All ProLiant DL360 power requirement discussions in this document are based on the input
power of the server since this number has direct impact in planning for the PDU selection and the
facility power source. One of the following methods can be used to account for the ProLiant
DL360 input power in the facility power distribution planning:
1. Use the maximum rated input power of 292W.
2. Use the de-rated input power, which can be calculated by subtracting the power budgets of
uninstalled optional components from the rated input power.