HP Proliant DL360 G6 Carrier-Grade Server Read Before Install

3 Power Supplies Specifications and Cable Information
Table 3-1 Power Supplies Specifications
ValueDescription
437573–B21HP 1200W PSU 48VDC Input Part Number
36–72Input Voltage Range (DCV)
DCFrequency Range (Nominal) (Hz)
724836Nominal Input Voltage (VDC)
120012001200Maximum Rated Output Wattage
192838Nominal Input Current (ACD)
136513501380Maximum Rated Input Wattage Rating (Watts)
136513501380Maximum Rated VA (Volt-Amp)
888987Efficiency (%) of Maximum Rated Output Wattage
n/an/an/aPower Factor
n/an/an/aLeakage Current (mA)
352520Maximum Inrush Current (A peak)
311Maximum Inrush Current duration (mS)
466246104713Maximum British Thermal Unit Rating (Btu-Hr)
NOTE: Battery return terminals are isolated DC returns (DC-I).
Power Cable Color Codes
Each DC power cable is shipped with a label that describes each lead. The label is located near
the pigtail leads. The three (3) leads are described in the following table:
Table 3-2 Power Cable Color Codes
DescriptionCable color
Positive returnBlack
Negative input voltageBlue
Safety groundGreen/Yellow
Replacing the Fans and Power Supplies
If a cooling fan or power supply fails, you must replace it. Replacement usually takes no longer
than five (5) minutes. For instructions on replacing these components, see the HP Proliant DL360
G6 Server Maintenance and Service Guide at the followingHP website:
http://www.hp.com/support/manuals
Under Servers, click Proliant ml/dl and tc series servers, and select your product.
Power Cable Color Codes 7