HP Proliant DL360 G6 Carrier-Grade Server Read Before Install

2 Cabling
Cable Information
This section provides cabling information for installing the HP Proliant DL360 G6 Carrier-Grade
Server.
NEBS Chassis Ground
This carrier-grade product is intended for use in both common bonding networks and isolated
bonding networks.
Network Cabling
Intra-building connections of the HP Proliant DL-series Carrier-Grade Servers require the use
of shielded cables grounded at both ends.
CAUTION: The intra-building ports of the equipment are suitable for connection to intra-building
or unexposed wiring or cabling only. The intra-building ports of the equipment must not be
metallically connected to interfaces that connect to the Outside Plant (OSP) or its wiring. These
interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports, as
described in GR-1089–CORE, Issue 4) and requires isolation from the exposed OSP cabling. The
addition of primary protectors is not sufficient protection to connect these interfaces metallically
to OSP wiring.
Cable Information 5