ProLiant DL360 Generation 4p Server (SAS Model) Maintenance and Service Guide
Removal and replacement procedures 17
Multi-bay device ejector
To remove the component:
1. Power down the server ("Powering down the server" on page 11).
2. Eject the multi-bay device or multi-bay device blank ("Multi-bay blank or device" on page 15).
3. Extend or remove the server from the rack ("Extending the server from the rack" on page 12).
4. Use a T-10 Torx screwdriver to remove the screws that secure the multi-bay device ejector to the
server chassis.
5. Press the tab on the side of the multi-bay device ejector to release it from the chassis.
6. Remove the multi-bay device ejector.
To replace the component, reverse the removal procedure.
Hot-plug AC power supply
This procedure assumes that the server is configured with two power supplies.
CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless all bays
are populated with either a component or a blank.
To remove the component:
1. Perform one of the following:
• If a conventional cable management solution is in place, unfasten the cable management solution
to access the power supply bays.
• If the cable management arm is in place, access the rear panel ("Accessing the product rear
panel" on page 13).
2. Disconnect the power cord.