ProLiant DL360 G4 and G4p Server High Density Deployment Solution White Paper

8
Figure 4. Fixed Cord Extension Bars
Single Extension Bar
Dual Extension Bars
Table 3 Fixed Cord PDUs
Description PDU Core Voltage Input. Extension
Bars
Outputs Part Number
Fixed Cord Extension
Bars (Worldwide)
No, but
compatible
with all cores
Either
Attached input
cord per stick:
IEC-320, C20
plugs into core
2
(14) IEC 320
C-13
351655-B21
Fixed Cord PDU
(NA/Japan)
Yes, 24A HV HV
Attached
modular core
input cord:
NEMA L6-30P
4
(28) IEC 320
C-13
351655-D72
Fixed Cord PDU
(International)
Yes, 32A HV HV
Attached
modular core
input cord:
IEC 309-32A
4
(28) IEC 320
C-13
351655-B31
The extension bars can be operated over the entire low-voltage (LV) to high-voltage (HV) range,
enabling the flexibility to apply to only the extension bar in either scenario. Since most installations
are either HV or LV, and do not typically change, it is the specific application that drives either the LV
or HV selection. The cores are specifically LV or HV by design and cannot be changed.
To determine actual power requirement per server instead of using the server nameplate rating, refer
to the ActiveAnswers Power Calculator
.