ProLiant Server High-Density Deployment Server Solution
Figure 4. Fixed cord extension bars
Single Extension Bar
Dual Extension Bars
Table 3 Fixed Cord PDUs
Description PDU Core Voltage Input. Extension
Bars
Outputs Part Number
Fixed Cord
Extension Bars
(Worldwide)
No, but
compatible
with all cores
Either
Attached input
cord per stick:
IEC-320, C20
plugs into
core
2
(14) IEC 320
C-13
351655-B21
Fixed Cord PDU
(NA/Japan)
Yes, 24A HV HV
Attached
modular core
input cord:
NEMA L6-30P
4
(28) IEC 320
C-13
351655-D72
Fixed Cord PDU
(International)
Yes, 32A HV HV
Attached
modular core
input cord:
IEC 309-32A
4
(28) IEC 320
C-13
351655-B31
The extension bars can be operated over the entire LV to HV range, enabling the flexibility to apply to
only the extension bar in either scenario. Since most installations are either HV or LV, and do not
typically change, it is the specific application that drives either the LV or HV selection. The cores are
specifically LV or HV by design and cannot be changed.
To determine actual power requirement per server instead of using the server nameplate rating, refer
to the ActiveAnswers Power Calculator
.
7