ProLiant Server High-Density Deployment Server Solution
Configuration C: Conventional
Table 9 describes a suggested configuration for 24 servers powered from a low-voltage AC power
supply.
Table 9. Configuration C Summary
Configuration C Summary
Rack Contents
Units
24 Servers with all fixed or all sliding rails with cable trays
4 Low-voltage 24-A 0U/1U PDUs
2 x 48-Port Ethernet switches
2 x 24-Port Ethernet hubs
1 IP Console Switch
24 Interface Adapters
2 Expansion Modules
1 x 1U Keyboard/Monitor
Internal Cables
24 power cords going to 4 PDUs in the side panels (These cables are supplied with the servers.)
28 KVM cables going from switch to server, switch to switch, and switch to 1U keyboard/monitor
24 management network cables from the iLO RJ-45 connector to two 24-port 10/100 Ethernet hubs
48 data network cables from the on-board 10/100/1000 NICs RJ-45 connectors to two 48-port
Ethernet switches each with 44 10/100T ports and 4 gigabit ports, assuming the use of two LAN
connections per server
Cables External to Rack
4 low-voltage input power cords connecting from the PDUs to facility AC power feeds
Site Utility Requirements (worst-case)
Power: 4 dedicated 100V - 120V 30-A branch circuits.
Thermal: Up to 48,000 BTUs/hour (This number is a worst-case. The actual BTUs/hour will depend on
the OS/application software running and the server hardware configurations.)
Weight: Up to 907.18 kg (2,000 lb). The network cables are not accounted for since most
implementations route the network cables to the ceiling-hung cable rails outside of the rack.
The use of the Double-Bar mounting brackets for the Modular PDU is highly recommended. This
enables the maximum number of outlets to be mounted on the same side of the rack enclosure as the
server power supply connection.
The use of the double-bar mounting brackets for the Modular PDU is highly recommended. This will
allow the maximum number of outlets to mounted on the same side of the rack enclosure as the server
power supply connection. The fixed length cord PDU significantly reduces cable bulk from power
cords. The PDU is 20 cm (8 in) long, and the cables are each 33 cm (13 in) long.
27