ProLiant DL360 G2 Server High-Density Deployment
ProLiant DL360 G2 Server High-Density Deployment 16
Table 9. Compaq PDUs (continued)
Dual Input / Transfer Switch PDUs (12 outlets, 0U/1U mounting)
191186-001
1
North America High 24 A 16 NEMA L6-30P
2 × 12-ft cord
12 × IEC 320-C13 4 × 10 A 4.37 × 30.48 × 43.18 cm
1.72 × 12.0 × 17.00 in
9.1 kg
20 lb
191186-B31
1
International High 30 A 20 IEC 309-32A
12-ft cord
12 × IEC 320-C13 4 × 10 A 4.37 × 30.48 × 43.18 cm
1.72 × 12.0 × 17.00 in
9.1 kg
20 lb
Note 1: This PDU supports power from two different sources. If one power source fails, the PDU uses the alternate source.
Note 2: This PDU must be hard-wired to the power source by a certified electrician.
Note 3: This PDU is using the maximum rated power supply input and not the de-rated values.
Note 4: This PDU family is scheduled to be discontinued on December 31, 2002.
Figuring Type and Number of PDUs
The type and number of PDUs required to power a full rack of servers depends on each server’s
power requirement, the number of servers deployed in the rack, and the available power for the
servers.
Compaq PDUs support both high-voltage and low-voltage applications. The input current rating
for a ProLiant DL360 G2 server is either 1.48 A at 200 to 240 volts or 2.80 A at 100 to 120 volts.
To determine the number of servers supported by a PDU, divide the PDU’s current rating by the
server’s total input current rating.
IMPORTANT: The examples shown in the following sections use the maximum rating of the
power supply. They are for reference only.
Example
One high-voltage PDU (P/N 252663-D72) has a current rating of 24 A. The server has a total
input current rating of 1.48 A at 208 volts.
24 A (PDU current rating) / 1.48 A (server total input current rating) = 16
This PDU can support a maximum of 16 servers at full server input current ratings.
Example
One low-voltage PDU (P/N 252663-D71) has a current rating of 24 A. The server has a total
input current rating of 2.80 A at 110 volts.
24 A (PDU current rating) / 2.80 A (server total input current rating) = 8
This PDU can support a maximum of 8 servers at full server input current ratings.
For more information on PDUs, refer to the website located at:
www.compaq.com/ups
Selecting Server Power Cords
The appropriate server power cord to use depends on the cable management system installed in
the rack. Generally, the sliding rail cable management system requires a power cord that is 1.8 m
(6 ft) in length. This length provides enough slack for the power cord to route through the cable
management arm.
1713-0702A-WWEN