ProLiant DL360 G2 Server High-Density Deployment
ProLiant DL360 G2 Server High-Density Deployment 13
Table 7. Measured Input Power for Optional Subsystem Components
Sub-system Components
Power Input
Typical / Peak
Intel Pentium III 1.40 GHz Processor
23 W / 26 W
128-MB DIMM
256-MB DIMM
512-MB DIMM
1-GB DIMM
1 W / 3 W
1 W / 3 W
1 W / 4 W
2 W / 5 W
18.2-GB HDD
36.4-GB HDD
72.8-GB HDD
16 W / 38 W
16 W / 38 W
16 W / 38 W
SA5302 9 W / 16 W
Note: DIMM and HDD input power can vary depending on the component and drive
manufacturer.
Input Power Budget De-rating
If a deployment plan limits the future expansion beyond certain configurations options, which
may be added in the future, then adjustments can be made to the expected input current and
thermal requirements of the servers.
• To de-rate the input power, start with the minimum configuration (Configuration 1 from
Table 6). Add the typical power of the components included in the desired system
configuration to calculate the de-rated power budget. Typical input powers for various
components are listed in Table 7.
Example
Assuming the desired server configuration is as follows; use Table 8 to calculate the de-rated
power budget using the typical power from Tables 6 and 7.
Processors: 2 x 1.40 GHz
Memory: 4 x 128 MB
Storage: 2 x 18.2 GB
Smart Array Controller 5302: 1 x SA5302
Table 8. Example De-rating Worksheet
Maximum Rated Input Power (in watts) for the base configuration Typical Power 146 W
1. Add the typical power for the second processor. 23 W
2. Add the typical power for the additional memory. 2 W
3. Add the typical power for the second HDD. 16 W
continued
1713-0702A-WWEN