ProLiant DL360 G2 Server High-Density Deployment 10
Table 4. ProLiant DL360 G2 Server Parameters (continued)
Component Weights (continued)
Maximum system measured input AC power
90 V 257 W
220 V 248 W
Maximum power supply rated input current
120 V 3.56 A
240 V 1.78 A
Maximum system measured input current
90 V 2.86 A
240 V 1.13 A
System Thermal Dissipation (per hour)
115 V 1,050 BTUs
240 V 1,050 BTUs
Relative Humidity (non-condensing)
Operating 10 to 90%
Non-operating 5 to 95%
The SA5302 option is a PCI card available from Compaq. Any third-party PCI cards used in the
ProLiant DL360 G2 server must comply with the industry-standard PCI specifications for
dimension, weight, power, and thermal requirements.
Power and Thermal Budgeting
Note: In this document, de-rating the input power budget means not using the maximum rated
input power values for the power supply. It is strongly recommended the installation planner
ensures the de-rated power budget satisfies all the installation requirements, including
future upgrade plans.
All ProLiant DL360 G2 power requirement discussions in this document are based on the input
power of the server, since this number has direct impact in planning for the PDU selection and the
facility power source. Use one of the following methods during the facility power distribution
planning to account for the ProLiant DL360 G2 input power.
1. Use the maximum rated input power of 308 W.
2. Use the Power Calculator Utility (provided in Active Answers) to configure your system as it
will be used; providing all the relevant power and cooling parameters needed to plan an
installation. For more information on the Power Calculator Utility, refer to our website
located at:
www.activeanswers.compaq.com/aaconfigurator/PowerCalc/DL360G2.xls
3. Use the de-rated input power, which can be calculated by adding the power budgets of
installed optional components from the rated input power.
4. Use the allocated input power, which can be calculated by dividing the maximum power of a
PDU by the number of servers. This calculated power should be at least 250 W to support all
the optional components initially released with the ProLiant DL360 G2.
1713-0702A-WWEN