ProLiant DL320 Server Maintenance and Service Guide

Removal and Replacement Procedures
2-38 Compaq ProLiant 320 Server Maintenance and Service Guide
COMPAQ CONFIDENTIAL Codename: DarkStar-T Part Number: 203834-003 Last Saved On: 12/28/01 9:29 AM
Power Supply
IMPORTANT: A “Fan 6 Error” indicates an error from one of the power supply fans. When this error
occurs, you must replace the entire power supply unit.
To remove the power supply:
1. Power down the server. See Powering Down the Server in this chapter.
2. Remove the access panel. See Server Access Panel in this chapter.
3. Remove the PCI riser board assembly. See PCI Riser Board Assembly in this chapter.
4. Remove the center wall. See Center Wall in this chapter.
5. Disconnect the hard drive power cables from the hard drives
.
6. Disconnect the power supply cable from the power supply connector on the system board
by pressing the locking tab on the side of the connector and pulling upwards .
7. Remove the two Phillips-head screws that secure the power supply unit to the chassis
.
8. Slide the power supply away from the back of the chassis and lift it from the server
.
3
2
1
1
4
3
Figure 2-32: Removing the power supply
Reverse steps 1 through 8 to replace the power supply.