Sliding Rails and Cable Management Solution
In a 22U rack that uses one PDU with a sliding rails cable management system, center the PDU in
the right side-panel of the rack.
Fixed Rails Cable Management Solution
In a 22U rack that uses one PDU with a fixed rails cable management system, center the PDU in
the left side-panel of the rack.
Installing Two PDUs in a 22U Rack
In a 22U rack that uses two PDUs, center one PDU in each side panel of the rack. This
configuration is the only one that supports installing one PDU on each side of the rack.
Installing PDUs in a 36U or 42U Rack
Before installing PDUs in a 36U or 42U rack, it may be necessary to remove the center support
bracket and center it between the PDUs. Install the PDUs on the same side of the rack as the cable
management tray (viewing the rack from the front). Use Figure 8 and Table 16 on the following
page to determine the position of PDUs in a 36 or 42U rack.