Compaq ProLiant DL320 Ultra-Dense Server Deployment in Compaq Racks
Compaq ProLiant DL320 Ultra-Dense Server Deployment in Compaq Racks 13
13AS-0900A-WWEN
Table 8. PDU configurations for 42U racks
Vertical Mount Bracket Kits
PDU
Input Voltage/
Current Rating
166097-B21
with Y-cables
191265-B21 Maximum
Servers
PDUs per
Rack
Populated Rack
Weight
BTUs
295363-001 Low/ 24 A 1 12 4 1,552 lb 28,644
295363-002 High/ 16 A 2 16 3 1,539 lb 28,644
295363-003 High/ 24 A 2 24 2 1,526 lb 28,644
295363-291 Low/ 24 A 1 12 4 1,552 lb 28,644
295363-B21 High/ 16 A 2 16 3 1,539 lb 28,644
295363-B32 High/ 16 A 2 16 3 1,539 lb 28,644
207590-B21 High/ 16 A 2 16 3 1,539 lb 28,644
207590-D71 Low/ 24 A 12 4 1,552 lb 28,644
207590-B31 High/ 32 A 2 24 2 1,539 lb 28,644
207590-D72 High/30 A 2 24 2 1,539 lb 28,644
191186-001 High/ 24 A 2 24 2 1,526 lb 28,644
191186-B31 High/30 A 2 24 2 1,526 lb 28,644
197617-002 High/ 32 A 2 24 2 1,526 lb 28,644
Table 9. PDU configurations for 36U racks
Vertical Mount Bracket Kits
PDU
Input Voltage/
Current Rating
166097-B21
with Y-cables
191265-B21 Maximum
Servers
PDUs per
Rack
Populated Rack
Weight
BTUs
295363-001 Low/ 24 A 1 12 3 1,273 lb 24,552
295363-002 High/ 16 A 2 16 3 1,273 lb 24,552
295363-003 High/ 24 A 2 24 2 1,260 lb 24,552
295363-291 Low/ 24 A 1 12 3 1,273 lb 24,552
295363-B21 High/ 16 A 2 16 3 1,273 lb 24,552
295363-B32 High/ 16 A 2 16 3 1,273 lb 24,552
207590-B21 High/ 16 A 2 16 3 1,273 lb 24,552
207590-D71 Low/ 24 A 12 3 1,273 lb 24,552
207590-B31 High/ 32 A 2 24 2 1,273 lb 24,552
207590-D72 High/30 A 2 24 2 1,273 lb 24,552
191186-001 High/ 24 A 2 24 2 1,260 lb 24,552
191186-B31 High/30 A 2 24 2 1,260 lb 24,552
197617-002 High/ 32 A 24 2 1,260 lb 24,552