Codename: ICE Part Number: 230852-002 Last Saved On: 11/20/02 4:51 PM
Optimum Environment
When installing the ProLiant BL p-Class system in a rack, select a location that meets
the environmental standards described in the following paragraphs.
Rack Requirements
The ProLiant BL p-Class system is compatible with the following racks:
42U, 36U, and 22U Compaq branded racks
Compaq branded 10000 and 9000 Series racks (42U, 36U, and 22U) are
compatible. (The system is optimized for 10000 Series racks.)
Compaq branded 7000 Series 42U racks require an extension kit (P/N
154392-B21) to increase rack depth from 83.82 cm (33 inches) to 93.98 cm
(37 inches). The 7000 Series 36U and 22U racks are not compatible.
Telco racks
Third-party rack cabinets that meet the following requirements:
Standard 48.26-cm (19-inch) width
Depth of 73.66 cm (29 inches) between front and rear RETMA rails
Minimum 7.62 cm (3 inches) clearance between rear RETMA rails and rear
rack door to accommodate system cabling
Front and rear doors must have a minimum of 65 percent open area to
provide adequate airflow
Space and Airflow Requirements
To enable servicing and adequate airflow, observe the following spatial requirements
when deciding where to install a Compaq branded, telco, or third-party rack:
Leave a minimum clearance of 63.5 cm (25 inches) in front of the rack.
Leave a minimum clearance of 76.2 cm (30 inches) in back of the rack.
Leave a minimum clearance of 121.9 cm (48 inches) from the back of the rack to
the rear of another rack or row of racks.