HP ProLiant BL p-Class System Setup and Installation Guide
Specifications
E-4 HP ProLiant BL p-Class System Setup and Installation Guide
HP CONFIDENTIAL
Writer: Christine Portillo File Name: j-appe Specifications.doc
Codename: ICE Part Number: 230852-002 Last Saved On: 11/20/02 5:01 PM
Table E-2: Operating and Performance Specifications for Power Enclosures
(North America/Japan)
continued
Item Single-Phase Model Three-Phase Model
Output voltage
specifications
Rated output voltage -48.8 VDC to -54 VDC -48.8 VDC to -54 VDC
Rated output current 99 A 170 A
Rated output power 4,298 W 8,310 W
Nominal power 4,158 W at 208 VAC 7,202 W at 208 VAC
Ambient temperature
range
1
Operating
10° to 35°C (50° to 95°F) 10° to 35°C (50° to 95°F)
Shipping -30° to 60°C (-22° to 140°F) -30° to 60°C (-22° to 140°F)
Relative humidity, noncondensing
2
Operating 20% to 80% 20% to 80%
Non-operating 5% to 95% 5% to 95%
Wet bulb temperature
Operating 28°C (82.4°F) 28°C (82.4°F)
Non-operating 38.7°C (101.7°F) 38.7°C (101.7°F)
1
Operating temperature has an altitude derating of 1°C (33.8°F) per 304.8 m (1,000 ft). No direct
sunlight. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit
is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude
maximum for storage is 70 KPa.