Power Enclosures
North America/Japan
Table E-2: Operating and Performance Specifications for Power Enclosures (North
America/Japan)
Item Single-Phase Model Three-Phase Model
Dimensions
Height 13.34 cm (5.25 in) 13.34 cm (5.25 in)
Depth 68.96 cm (27.15 in) 68.96 cm (27.15 in)
Width 44.7 cm (17.60 in) 44.7 cm (17.60 in)
Weight
No hot-plug power
supplies
21.55 kg (47.5 lb) 21.55 kg (47.5 lb)
All hot-plug power
supplies
45.13 kg (99.5 lb) 56.93 kg (125.5 lb)
Input requirements
Rated input voltage 200 VAC to 240 VAC 200 VAC to 240 VAC line to line,
three-phase (3W+G)
Rated input frequency 50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current
per side
24 A 24 A per phase
Rated input power per
side
5,760 W 9,976 W
Power plug 1 NEMA L6-30P per side 1 NEMA L15-30 per side
continued