HP ProLiant BL e-Class System Setup and Installation Guide
Specifications
Server Blade Enclosure
Table F-1: Enclosure Operating and Performance Specifications
Dimensions
Height 13.34 cm (5.25 in)
Depth 68.58 cm (27 in)
Width 48.26 cm (19 in)
Weight with patch panel
No server blades 26.76 kg (59 lb)
20 server blades 42.64 kg (94 lb)
Input requirements
Rated input voltage 100 to 127 VAC (200 to 240 VAC)
Rated input frequency 47 to 63 Hz
Rated input current 8.5A at 120 VAC (4.3A at 240 VAC)
Rated input power 1000 W
BTUs per hour 3416
Temperature range
1
Operating
10° to 35°C (50° to 95°F)
Shipping, 72 hours
-40° to 60°C (-40° to 140°F)
Relative humidity
(noncondensing)
2
Operating 10% to 90%
Non-operating 10% to 95%
1
Operating temperature has an altitude derating of 1°C per 304.8 m (1.8°F
per 1000 ft). No direct sunlight.
2
Storage maximum humidity of 95% is based on a maximum temperature of
45°C (113°F). Minimum pressure for storage is 70 KPa.