Installation and Getting Started Guide for HP 600/610/620/630 RPS/EPS 2011-04
5-9
Installing and Connecting the HP Redundant / External Power Supplies
Installation Procedures
Rack or Cabinet Mounting
These power supplies are designed to be mounted in any EIA-standard 19-inch
telco rack or communication equipment cabinet. The mounting brackets have
multiple mounting holes and can be rotated allowing for a wide variety of
mounting options.
WARNING For safe operation, please read the Installation Precautions on
page 5-6, before mounting the unit.
For safe reliable installation, only use the screws provided in the
accessory kit to attach the mounting brackets to the power supply.
Equipment
Cabinet
Note
The 12-24 screws supplied with the unit are the correct threading for standard
EIA/TIA open 19-inch racks. If you are installing the unit in an equipment
cabinet such as a server cabinet, use the clips and screws that came with the
cabinet in place of the 12-24 screws that are supplied with the unit.
Rack mounting the 600, 610 and 620 power supplies:
1. Use a #1 Cross-head screwdriver and attach the mounting brackets to the
unit with the included 8-mm M4 screws. The screws must be tightened
sufficiently to provide proper support for the unit in the rack.
Figure 5-1. Example one, connecting mounting brackets