HP Power Protector User Guide

Configuration and operation 62
Upon reset, the value defaults to the maximum value of 99999 seconds.
The Operating system shutdown time value entered for the HPPP Administrator must be equal to or
greater than the HPPP Client configured with the greatest operating system shutdown time.
After the operating system shutdown begins, the shutdown process cannot be canceled, even if utility
power is restored.
For load shedding, each Client shuts down based on the delay settings for that Client. This increases the
backup time for the remaining Clients.
The UPS powers down after all load segments power down.
If any other condition happens during the initiated shutdown, such as the battery capacity is under limit,
the HPPP Administrator sends a shutdown command to all Clients to start the shutdown process earlier.
The following example shows the shutdown parameters for a UPS with two load segments, one connected
server that has HPPP Administrator installed, and three connected servers that have HPPP Clients installed on
each server.
Item Description
1
Utility failure
2
Utility restore
3
Utility
4
Client 1 on load segment 1
5
Client 2 on load segment 1
6
Load segment 1
7
Client 3 on load segment 2
8
Administrator on load segment 2
9
Load segment 2
10
UPS
On utility
On battery (Shutdown initiated after)
Operating system shutdown time