FW 07.00.00/HAFM SW 08.06.00 McDATA Products in a SAN Environment Planning Manual (620-000124-500, April 2005)

A-4
McDATA Products in a SAN Environment - Planning Manual
Product Specifications
Eclipse 1620 SAN Router:
Input voltage: 100 to 240 VAC.
Input current: 0.35 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Eclipse 2640 SAN Router:
Input voltage: 100 to 240 VAC.
Input current: 0.95 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Heat Dissipation
McDATA products have the following maximum heat dissipation
characteristics:
Intrepid 6064 Director: 490 watts (1,672 BTU/hr).
Intrepid 6140 Director: 841 watts (2,873 BTU/hr).
Intrepid 10000 Director: 2,496 watts (8,517 BTU/hr).
Sphereon 3232 Switch: 245 watts (836 BTU/hr).
Sphereon 4300 Switch: 37 watts (127 BTU/hr).
Sphereon 4500 Switch: 49 watts (167 BTU/hr).
Eclipse 1620 SAN Router: 73 watts (239 BTU/hr).
Eclipse 2640 SAN Router: 198 watts (676 BTU/hr).
Clearances
McDATA products have the following cooling airflow clearances. In
addition, the Intrepid 10000 Director may require removal from an
equipment cabinet (left-side service clearance required) for FRU
removal and replacement.
Intrepid 6064 Director:
Right and left side: 5.1 centimeters (2.0 inches).
Front and rear: 7.6 centimeters (3.0 inches).
Top and bottom: No clearance required.
Intrepid 6140 Director:
Right and left side: 2.5 centimeters (1.0 inches).
Front and rear: 7.6 centimeters (3.0 inches).
Top and bottom: No clearance required.