Neoview Owner's Manual (R2.2)
Environmental Specifications
Unit Heat (both PDUs powered - BTU
per hour)
Unit Heat (single PDU powered - BTU
per hour)
Cabinet Type
1906015880Segment
Combination:
329782824916-node configuration
552184675932-node configuration
774586527048-node configuration
996988378164-node configuration
14417812080296-node configuration
196776164941128-node configuration
383210320539256-node configuration
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range
21
Operating Range
1
Specification
9× F (5× C) Repetitive 36× F
(20× C) Nonrepetitive
68× to 72× F (20× to 25× C)41× to 95× F (5× to 35× C)Temperature (all except
FCDM and Data Loader)
0.6× F (1× C) Repetitive 1.6×
F (3× C) Nonrepetitive
-50× to 95× F (10× to 35× C)Temperature (Data Loader
and FCDM)
6%, noncondensing40% to 50%, noncondensing15% to 80%, noncondensingHumidity (all except Data
Loader)
6%, noncondensing40% to 50%, noncondensing10% to 70%, noncondensingHumidity (Data Loader)
--0 to 10,000 feet (0 to 3,048
meters)
Altitude
2
1 Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm)
from the front of the air intake cooling vents.
2 For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5× F
(0.83× C) from the upper limit of the operating and recommended temperature ranges.
Environmental Specifications 31