Neoview Owner's Manual (R2.2)

Grounding
A safety ground/protective earth conductor is required for each AC service entrance to the
segment and combination cabinets. This ground must comply with local codes and any other
applicable regulations.
Branch Circuits and Circuit Breakers
Each of the PDUs requires a separate branch circuit of these ratings:
AmpsVoltsRegion
24208North America and Japan
40200 - 240North America and Japan
16380 - 415International
32200 - 240International
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Cabinet Power Loads
In normal operation, the AC power is split equally between the two PDUs in a cabinet. However,
if one of the two AC power feeds fails, the remaining AC power feed and PDU must carry the
power for all components in that cabinet.
Peak Inrush Current
(amps)
Volt-Amps TotalApparent Power
(volt-amps measured
on a single PDU with
both PDUs
powered)Volt-Amps
per PDU
Apparent Power
(volt-amps measured
on a single PDU with
one PDU powered)
Cabinet Type
558027904650Segment
Combination:
96659665827916-node configuration
16183161831370432-node configuration
22701227011912948-node configuration
29219292192455464-node configuration
42255422553540496-node configuration
576705767048340128-node
configuration
11230911230993942256-node
configuration