Neoview Owner's Manual (R2.2)
North America and Japan 200 to 240 V AC Input, Single Phase, 40A RMS Modular Cabinet
• EIA standard 19-inch rack with 42U of rack space
• Geography: North American and Japan
• Recommended for most configurations
• Two power distribution units (PDU), zero-U rack design
• PDU input characteristics
— 200 to 240 V ac, single phase, 40A RMS, 3-wire
— 50/60Hz
— Non-NEMA Locking CS8265C, 50A input plug
— 6.5 feet (2 m) attached power cord
• PDU output characteristics
— 3 circuit-breaker-protected 20A load segments
— 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
— 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
• Front and rear doors
International 380 to 415 V AC Input, 3-Phase Wye, 16A RMS Modular Cabinet
• EIA standard 19-inch rack with 42U of rack space
• Geography: International
• Recommended for most configurations
• Harmonized power cord
• Two power distribution units (PDU), zero-U rack design
• PDU input characteristics
— 380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
— 50/60Hz
— IEC309 5-pin, 16A input plug
— 6.5 feet (2 m) attached power cord
• PDU output characteristics
— 3 circuit-breaker-protected 16A load segments
— 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
— 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
• Includes front and rear doors
International 200 to 240 V AC Input, Single Phase, 32A RMS Modular Cabinet
• EIA standard 19-inch rack with 42U of rack space
• Geography: International
• Harmonized power cord
• Recommended for most configurations
• Two power distribution units (PDU), zero-U rack design
• PDU input characteristics
— 200 to 240 V ac, single phase, 32A RMS, 3-wire
— 50/60Hz
— IEC309 3-pin, 32A input plug
— 6.5 feet (2 m) attached power cord
• PDU output characteristics
— 3 circuit-breaker-protected 20A load segments
— 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
— 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
• Front and rear doors
28 Installation Specifications for the Neoview Platform