Neoview Owner's Manual (R2.2)

Supported PDUs and Power Offerings
The Neoview platform PDUs are available in four static strapping configurations that are
factory-installed in a segment or combination cabinet. The specific PDU strapping configuration
for a particular site depends on the type and voltage of AC power at the intended installation
site:
“North America and Japan 208 V AC Input, 3-Phase Delta, 24A RMS Modular Cabinet”
(page 27)
“North America and Japan 200 to 240 V AC Input, Single Phase, 40A RMS Modular Cabinet”
(page 28)
“International 380 to 415 V AC Input, 3-Phase Wye, 16A RMS Modular Cabinet” (page 28)
“International 200 to 240 V AC Input, Single Phase, 32A RMS Modular Cabinet” (page 28)
North America and Japan 208 V AC Input, 3-Phase Delta, 24A RMS Modular Cabinet
EIA standard 19-inch rack with 42U of rack space
Geography: North America and Japan
Recommended for most configurations
Two power distribution units (PDU), zero-U rack design
PDU input characteristics
208 V ac, 3-phase delta, 24A RMS, 4-wire
50/60Hz
NEMA L15-30 input plug
6.5 feet (2 m) attached power cord
PDU output characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
Front and rear doors
AC Input Power 27