Site Preparation Guide, Fifth Edition - HP Integrity Superdome and HP 9000 Superdome
Chapter 4
Environmental Requirements
Air Flow
39
Air Flow
hp Integrity Superdome and hp 9000 Superdome systems require the cabinet air intake temperature to be
between 20
ο
C and 30
ο
C at 2400 CFM. Any cooling system layouts described in Chapter 2 can be adapted to
cool the system.
Figure 4-1 on page 39 illustrates the location of the inlet and outlet airducts on a single cabinet.
Figure 4-1 Airflow Diagram
Air Flows Front to Top