Site Preparation Guide, Fifth Edition - HP Integrity Superdome and HP 9000 Superdome
Chapter 3
Electrical Specifications
I/O Expansion Cabinet Power Requirements
28
I/O Expansion Cabinet Power Requirements
The I/O expansion cabinet requires a single phase 200-240VAC input. Table 3-5 lists the AC power
requirements for the I/O expansion cabinet.
NOTE The IOX accommodates two AC inputs for redundancy
Table 3-5 I/O Expansion Cabinet Power Requirements (without Support
Management Station)
Requirements Value
Nominal input voltage 200/208/220/230/240 (VAC rms)
Input voltage range (minimum-maximum) 200-240 (VAC rms)
Frequency range (minimum-maximum) 50/60 (Hz)
Number of phases 1
Marked Electrical input current 16A
Maximum inrush current 60 max (A peak)
Power factor correction 0.95 minimum
Table 3-6 I/O Expansion Cabinet Component Power Requirements
Power Required (50 - 60 Hz) VA
Fully configured cabinet 3200
I/O cardcage 500
ICE 600