Site Preparation Guide, Fifth Edition - HP Integrity Superdome and HP 9000 Superdome
Chapter 3
Electrical Specifications
Power Options
25
Customer Installation Options
Figure 3-10 and Figure 3-11 detail a suggested configuration for connecting the PDCA when the use of rigid
conduit is required or desired. Using a 2- to 4-inch nipple and a 90o elbow allows the conduit to pass through
the raised floor at a point immediately past the cabinet. This prevents the conduit from extending beyond the
cabinet.
Figure 3-10 PDCA Conduit Connection
Figure 3-11 Conduit Required for PDCA Connection
8/18/00
60SP046A
L3-L1 L2-L3 L1-L2
N
L3
8/18/00
60SP045A
L3-L1 L2-L3 L1-L2
N
L3