Electrical Specifications
Circuit Breaker
15
Circuit Breaker
Each cabinet using a three-phase, four-wire input requires dedicated circuit breaker to support the Marked
Electrical current of 44A per phase. The facility electrician and local service codes will determine proper
circuit breaker selection.
Each cabinet using a three-phase five-wire input requires a dedicated circuit breaker to support the Marked
Electrical current of 24A per phase. The facility electrician and local service codes will determine proper
circuit breaker selection.
NOTE When using the minimum sized breaker, always choose circuit breakers with the maximum
allowed trip delay to avoid nuisance tripping.