NonStop NS14000 Series Planning Guide (H06.13+)
International: 380 to 415 V AC, Modular Three-Phase PDUs and Extension Bars
The international PDU power characteristics are:
PDU input characteristics
• 380 to 415 V AC, 3-phase Wye, 16A RMS, 5-wire
• 50/60Hz
• IEC309 5-pin, 16A input plug
• 12 feet (3.6 m) attached power cord
6 AC IEC 320 C19 receptacles per PDU with 20A
circuit-breaker labels (L1, L2, L3, L4, L5, and L6)
PDU output characteristics
Extension bar input characteristics
• 200V to 240 V AC, 3-phase delta, 16A max RMS,
4-wire
• 50/60Hz
• IEC 320–C20 input plug
• 6.5 feet (2.0 m) attached power cord
7 AC IEC 320 C13 receptacles per PDU with 12A
maximum per outlet
Extension bar output characteristics
Branch Circuits and Circuit Breakers, Modular Three-Phase PDUs
Modular cabinets for the NonStop NS14000 series system that use a three-phase power
configuration with modular three-phase PDUs contain two PDUs. In cabinets without the optional
rack-mounted UPS, each of the two PDUs requires a separate branch circuit of these ratings:
Amps (see following “CAUTION”)Volts (Phase-to-Phase)Region
30200 to 240North America and Japan
16
1
380 to 415International
1
Category D circuit breaker is required.
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical codes
and regulations.
NOTE: If your system includes the optional rackmounted HP R5000 UPS or HP R5500 XR UPS,
the modular cabinet will have one PDU located on the rear left side and four extension bars on
the rear right side. To provide redundancy, components are plugged into the left-side PDU and the
extension bars. Each extension bar is plugged into the UPS.
Branch circuit requirements vary by the input voltage and the local codes and applicable regulations
regarding maximum circuit and total distribution loading. Select circuit breaker ratings according
to local codes and any applicable regulations for the circuit capacity.
Select circuit breaker ratings according to local codes and any applicable regulations for the circuit
capacity. Note that circuit breaker ratings vary if your system includes the optional rackmounted
HP R5000 UPS or HP R5500 XR Integrated UPS.
Modular Three-Phase PDUs 57