HP Insight Remote Support 7.0.9 Monitored Devices Configuration Guide

Verify Communication Between Monitored Device and
Insight RS
To verify communication between your monitored device and Insight RS, complete the following steps:
Send a Test Trap
To send a test trap, complete the following steps:
1. Log on to the UPS Network Module web interface.
2. In the left menu, click Notified Applications, then click Add Trap Receiver. Up to three
applications can be configured to receive SNMP traps from the UPS Network Module.
3. Click Utility Failure Test. The UPS Network Module sends a Utility failure trap, and then sends a
Utility restored trap 30 seconds later.
4. Verify that Insight Remote Support received the test trap.
HP Insight Remote Support 7.0.9:Monitored Devices Configuration Guide Page 253 of 267
Chapter 34: Configuring Uninterruptable Power Supplies