HP Insight Remote Support 7.0.9 Monitored Devices Configuration Guide
Fulfill Configuration Requirements
To configure your UPS Network Modules to be monitored by Insight RS, complete the following steps:
Task Complete?
Make sure Insight RS supports your UPS Network Module by checking the HP Insight
Remote Support Release Notes.
Configure SNMP on the UPS Network Module and set the Hosting Device as a trap
receiver.
Add the SNMP protocol to the Insight RS Console.
Discover the UPS Network Module in the Insight RS Console.
Send a test event to verify connectivity between your UPS Network Module and Insight
RS.
Table 34.2 UPS Network Module Configuration Steps
Install and Configure Communication Software on Network
Modules
To configure your monitored devices, complete the following sections:
Configure SNMP
SNMP can be setup in the SNMP Settings screen in the UPS Network Module web interface. The SNMP
Settings screen allows an administrator to configure SNMP settings for computers that use the HP Power
MIB to request information from the UPS Network Module.
For more details about configuring SNMP, see the HP UPS Network Module User Guide.
To configure SNMP, complete the following steps:
1. Log on to the UPS Network Module web interface.
2. In the left menu, click SNMP.
HP Insight Remote Support 7.0.9:Monitored Devices Configuration Guide Page 250 of 267
Chapter 34: Configuring Uninterruptable Power Supplies